dc.description.abstract | Reduction of data centre power consumption is a timely challenge. Waste heat reuse is another focus area when developing energy efficient and sustainable data centres. And these two issues are interconnected through liquid cooling of server racks and/or direct-to-chip liquid cooling. Both of these solutions make it possible to transfer a significant proportion of the waste heat energy back to profitable use. Nevertheless, the heat reusing opportunity is not the only benefit direct-to-chip liquid cooling may offer. Another benefit is the notable reduction of power consumption related to cooling fans associated with server blades and rack-level cooling systems.
To evaluate this benefit, we performed power consumption and performance measurements in a subarctic supercomputer centre hosting a cluster of 632 blade nodes. Our study concentrated on a 47-node subset that we analysed when the servers were executing the LINPACK benchmark. Our conclusion is that direct-to-chip liquid cooling can reduce the total power consumption, in this case, up to 14.4% depending on the inlet air temperature. | en_US |
dc.description | Publisher's pdf. Source at <a href=http://doi.org/10.1504/IJHPCN.2016.076269>http://doi.org/10.1504/IJHPCN.2016.076269</a> | en_US |
dc.identifier.citation | Ovaska, SJ; Dragseth, RE; Hanssen, SA: Direct-to-chip liquid cooling for reducing power consumption in a subarctic supercomputer centre. International Journal of High Performance Computing and Networking. 2016;9(3):242-249 | en_US |
dc.identifier.cristinID | FRIDAID 1384502 | |
dc.identifier.doi | 10.1504/IJHPCN.2016.076269 | |
dc.identifier.issn | 1740-0562 | |
dc.identifier.issn | 1740-0570 | |
dc.identifier.uri | https://hdl.handle.net/10037/10887 | |
dc.language.iso | eng | en_US |
dc.publisher | Inderscience | en_US |
dc.relation.journal | International Journal of High Performance Computing and Networking | |
dc.rights.accessRights | openAccess | en_US |
dc.subject | VDP::Teknologi: 500::Informasjons- og kommunikasjonsteknologi: 550::Datateknologi: 551 | en_US |
dc.subject | VDP::Technology: 500::Information and communication technology: 550::Computer technology: 551 | en_US |
dc.subject | data centre | en_US |
dc.subject | direct-to-chip liquid cooling | en_US |
dc.subject | power consumption | en_US |
dc.subject | subarctic climate | en_US |
dc.subject | supercomputer | en_US |
dc.subject | waste heat reuse | en_US |
dc.title | Direct-to-chip liquid cooling for reducing power consumption in a subarctic supercomputer centre | en_US |