dc.contributor.author | Bi, Yang | |
dc.contributor.author | Aganovic, Amar | |
dc.contributor.author | Mathisen, Hans Martin | |
dc.contributor.author | Cao, Guangyu | |
dc.date.accessioned | 2022-11-22T11:22:17Z | |
dc.date.available | 2022-11-22T11:22:17Z | |
dc.date.issued | 2022-04-21 | |
dc.description.abstract | The purpose of this study was to reveal the exposure level of surgical staff to severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) from the patient's nose and wound during operations on COVID-19 patients. The tracer gas N<sub>2</sub>O is used to simulate SARS-CoV-2 from the patient's nose and wound. In this study, concentration levels of tracer gas were measured in the breathing zones of these surgical staff in the operating room under three pressure difference conditions: −5 pa–15 pa and −25 pa compared to the adjunction room. These influencing factors on exposure level are analyzed in terms of ventilation efficiency and the thermal plume distribution characteristics of the patient. The results show that the assistant surgeon faces 4 to 12 times higher levels of exposure to SARS-CoV-2 than other surgical staff. Increasing the pressure difference between the OR lab and adjunction room can reduce the level of exposure for the main surgeon and assistant surgeon. Turning on the cooling fan of the endoscope imager may result in a higher exposure level for the assistant surgeon. Surgical nurses outside of the surgical microenvironment are exposed to similar contaminant concentration levels in the breathing zone as in the exhaust. However, the ventilation efficiency is not constant near the surgical patient or in the rest of the room and will vary with a change in pressure difference. This may suggest that the air may not be fully mixed in the surgical microenvironment. | en_US |
dc.identifier.citation | Bi Y, Aganovic A, Mathisen HM, Cao G. Experimental study on the exposure level of surgical staff to SARS-CoV-2 in operating rooms with mixing ventilation under negative pressure. Building and Environment. 2022;217 | en_US |
dc.identifier.cristinID | FRIDAID 2048389 | |
dc.identifier.doi | 10.1016/j.buildenv.2022.109091 | |
dc.identifier.issn | 0360-1323 | |
dc.identifier.issn | 1873-684X | |
dc.identifier.uri | https://hdl.handle.net/10037/27459 | |
dc.language.iso | eng | en_US |
dc.publisher | Elsevier | en_US |
dc.relation.journal | Building and Environment | |
dc.relation.uri | https://www.sciencedirect.com/science/article/pii/S0360132322003286 | |
dc.rights.accessRights | openAccess | en_US |
dc.rights.holder | Copyright 2022 The Author(s) | en_US |
dc.rights.uri | https://creativecommons.org/licenses/by/4.0 | en_US |
dc.rights | Attribution 4.0 International (CC BY 4.0) | en_US |
dc.title | Experimental study on the exposure level of surgical staff to SARS-CoV-2 in operating rooms with mixing ventilation under negative pressure | en_US |
dc.type.version | publishedVersion | en_US |
dc.type | Journal article | en_US |
dc.type | Tidsskriftartikkel | en_US |
dc.type | Peer reviewed | en_US |